Sophia Aguilar A tie breaker connects both main buses and is normally closed, allowing for more flexibility in operation. A fault on one bus requires isolation of the bus while the circuits are fed from the opposite bus.
The 2 main breakers and tie-breakers are vaccum breakers that have a kirk key interlock system in place to ensure that the ties and both mains are never all closed at once putting transformers in parallel.
Using the U.S. National Electrical Code as an example, common internal trip ties on circuit breaker toggle switch handles are required by NEC 240.20 (B) in some cases, such as when the circuit breaker pair is powering a 240VAC circuit or on a multi wire branch circuit sharing a common neutral wire. (B) Disconnecting Means.
If one transformer fails or is taken out of service for maintenance the Tie breaker can be closed to provide power to both MCC from the remaining transformer. Also, depending upon how the distribution system is set up there are some other things that must be considered. There is with almost all certainty a main breaker for each source.
What is a tie breaker?
A Tie breaker is normally a breaker that can be closed to connect two separate systems together. An example is you have two 2000 amp 480 volt MCC panels, each fed from a transformer. If one transformer fails or is taken out of service for maintenance the Tie breaker can be closed to provide power to both MCC from the remaining transformer.
It is important that the source being used to supply the power have the capacity to supply the additional load or some of the load must be shed . The second concern is that the main breaker of the source that has failed must be opened with almost all certainty before closing the tie breaker.
It is common it use a kirk key interlock scheme to prevent the closing of the tie breaker unless one of the main breakers is opened first. If that main breaker is not opened first you could back feed into the utility as well as a possibility that the sources may be out of phase when paralleled with the other.
It’s pretty common in process industry. Any I’ve worked with, the customer is big load (read big payer ) The utilities are generally co-operatives and big, long-term payers help with the economy of scale and keep the price down for the majority of the owners/users (residential). So the utilities are right there helping all they can.
There is with almost all certainty a main breaker for each source. As stated in the previous post the one of the more common objectives of a tie breaker to feed the other distribution system should its source fail.
What is a tandem circuit breaker?
Tandem circuit breakers (two breakers powering two circuits fit into a single original breaker slot in a panel) also trip together.
Using the U.S. National Electrical Code as an example, common internal trip ties on circuit breaker toggle switch handles are required by NEC 240.20 (B) in some cases, such as when the circuit breaker pair is powering a 240VAC circuit or on a multi wire branch circuit sharing a common neutral wire.
ADVERTISEMENT
There the yellow plastic ties indicate pairs of tandem circuit breakers that are powering multiwire branch circuits.
6.1.5.3 Single-pole circuit breakers rated at 120/240 V ac or 125/250 V DC shall have provision for the use of handle ties. Handle ties, when installed, shall:
The concern is that where a pair of joined circuit breakers must be installed so that if either trips, both breakers will switch off, if instead the handle tie or breaker design could permit just one breaker to turn off while the other remains on, the circuit is unsafe.
Even if a circuit breaker pair can be physically connected by a common handle ( not possible in the case of Pushmatic™ breakers) the level of protection is not the same as that provided by two-pole or double-pole circuit breakers with a common internal trip tie mechanism.
Siemens sells an add-on handle tie for joining circuit breakers, used with BQ, BQH, HBQ, BLH, HBL Circuit Breakers but yours appear to be a different breaker brand and model.